Skip to main content
  • Research article
  • Open access
  • Published:

Microclimate numerical simulation to obtain the minimum safe distances between a painted wood panel and the inner face of an exterior wall

Abstract

This study provides a detailed understanding of the heat fluxes and temperatures that take place in the channel between the inner face of an exterior wall and the back of a painted wood panel hung on it. This is performed by means of a numerical simulation with a 2 dimensional CFD software. Distributions of temperatures, heat fluxes, and other parameters are quantified for 56 cases where the classical equationsRaithby-Hollands and similar—cannot be applied as these require vertical isothermal plates or isofluxes. Studied scenarios include different panel heights, channel widths, and room heights. Combining these data with outside temperature (− 3 °C) and heating air supply temperature (20 °C), to provide a nearly constant 19.6 °C in the room except in the channel between panel and wall, and with two values of specific humidity in the room, we provide for every studied case, advised distances, for these conditions, between the panel and the wall.

Introduction

If we place an easel painting or a painted wood panel in the interior face of an exterior wall (either touching the wall or very close to it) both act as thermal insulators. So, in historical buildings with non-thermally insulated exterior walls and low outside temperatures, the inside wall face and the painting back temperatures can drop some degrees below the room temperature and consequently the relative humidity (RH) in these places can rise to unacceptable levels for the proper conservation of paintings [1]. Neuhaus [2] states that in this case, spacers shall be placed between paintings and wall in order to provide insulation at the painting back but required distances are not provided.

Fig. 1
figure 1

Sketch room/panel case 12 ht = 3 m, h = 1 m, h1 = 1 m, s = 20 mm

In Padfield previous study [3] temperature and RH have been measured on site and a minimum distance of 20 mm has been recommended between a 35 cm high framed painting and the inner face of a window facing north. Although broader distances have been suggested for bigger artefacts, specific values have not been calculated for this or other scenarios.

The aim of this research is not to set the exhibition room climatic conditions in historical buildings, which today in Europe are established by the CEN recommendations but to calculate the temperatures and heat flux distributions in the channel between a cold exterior wall and painted wood panels of different sizes placed at varying distances from the wall and at two different relative humidity values, to extend the general recommendation given in the Padfield study. Performing measurements on site requires large number of tests in different and very accurate environment conditions. The differential equations that model heat transfer in fluids take into account three fundamental laws as the mass, momentum and energy conservation, and thus theoretically, they can solve the heat transfer simulation between the fluid and the boundaries in whatever complex geometry. However, as they are in not linear partial derivatives, they can be solved analytically only in a few particular cases through dimensional analysis and simplifications.

Heat transfer between two parallel vertical isothermal and isoflux plates through the air by natural convection has been well parametrized by Raithby-Hollands [4], Bar-Cohen [5], Cadafalch-Oliva [6], Spalding [7, 8], and others, but as the exterior wall and the wood panel are neither isothermal and nor isoflux plates, their equations cannot be applied.

Instead, at present, CFD tools offer the possibility to solve numerically differential equations that model heat transfer in our selected geometry and materials with enough accuracy and at a reasonable cost. The commercial 2D fluid mechanics software EasyCFD_G developed and tested by A. Gameiro of the Coimbra University [9,10,11,12,13,14], is used in this research to extend the only existing single recommendation, up to now, of minimum 20 mm for the distance between a “cold” external wall in historical buildings and a painting hung on it.

This tool allows us to use the (k-ω) or the (k-ε) equations, where k is for turbulent kinetic energy, ɛ for its dissipation rate, ω for the turbulent kinetic energy frequency of dissipation, according to the distance from each mesh element to the boundaries and to quantify some magnitudes, raised in the Grau-Bové and Strlic article [15] such as the turbulence and the thermal fluxes in each mesh element, distinguishing between the contributions by convection and conduction.

These simulations show important vertical temperature gradients at the wall and the wood panel back when the room heating air supply (20 °C) provides a nearly constant value (19.6 °C ± 0.3 K) around the room (except in corners and in the space between the back of the panel and the wall).

The specific humidity (SH) is considered constant in all the room. The possible water buffer action from the boundary surfaces (walls and panel) is not considered, as the simulations are done for a steady state and this allows to simplify the problem and to get an easier understanding of the heat fluxes involved. Two SH scenarios are considered (7.5 g/kg and 8.7 g/kg) which correspond to 52% RH and 60% RH both at 19.6 °C.

From this point on, Wall refers to the inner face of the exterior wall, Back to the wood panel surface facing the channel and Front to the wood panel surface facing the room. Also the space between the inner side of the exterior wall and the back of the panel is named channel.

Materials and methods

Simulation description

We have built 8 different 2-dimensional CFD “models”, each of them composed by a vertical cross-section of a room 3 m wide with a 2 cm thick wood panel hanging at different distances (“s”) from the Wall. From this point on, the word panel will be used with the same meaning as wood panel.

All the models also have the same following features: heating system by hot air forced convection, distance from the panel centre to the floor (1.5 m) and boundary conditions. The difference among the 8 models lies in the following variables: different panel height “h” (2 m, 1 m and 0.5 m), different room height “ht” (3 m and 6 m) to quantify the effect of the distance travelled by the air along the cooled inner face of the Wall before entering in the channel, one model without the panel (for comparison) and another model in a room 6 m high with a cornice 15 cm high and 5 cm wide protruding from the inner side of the outside wall at 30 cm above the wood panel.

For each of the 8 described models, there are different “cases” (one for each distance “s” from panel to wall), see Table 1. Combining all the mentioned variables, we get 45 basic cases. All basic cases and models are listed in Table 1. See sketch in Fig. 1.

Table 1 Summary of the 45 basic cases data

Doing it we have simulated 45 basic cases where in a heated room of different heights, painted wood panels of different dimensions (models) are hung at different short distances on the inner face of an exterior wall.

In these simulations we got air velocities (u horizontal and v vertical), temperatures (Tw wall, Tb back and Ta air), heat fluxes and turbulence intensity (Tu) for each of all the CFD mesh elements in the room (between 43943 and 182261). Thus, we have exported the temperatures and heat fluxes distribution from 100 points located in three vertical layers along the panel height: along the Back, along the Front and along the Wall. Knowing these temperatures distribution and the SH in the room, we have calculated the RH values in these same 100 points for the two SH scenarios.

Besides, we also got the air velocities and turbulence intensity along the channel that helps to improve the understanding of the heat and mass transfer through the channel. Comparing the exported values, we have seen that in addition to the classical non-dimensional number s/h (channel width/wood panel height) there are other parameters (as the distances from the ceiling to the panel or the possibility of eddies at the channel inlet and outlet) that can modify the temperature and the heat flux distribution in the channel.

Heat transfer parameters and room conditions

Walls and wood panel heat conduction

The room floor, the roof and the inner wall are adiabatic. The exterior wall is limestone 41 cm thick, and includes a 1 cm mortar layer. The exterior wall parameters are: thermal conductivity kh = 1.8 W/m K, density ρ = 2095 kg/m3, and specific heat or fluid heat capacity cp = 903 J/kg K, all including the correction factor for the mortar layer. The parameters used for the wood panel are: kh = 0.2 W/m K, ρ = 700 kg/m3, and cp = 1600 J/kg K.

Although as stated in the Fourier equation \(\rho c_{p} \frac{\partial T}{\partial t} = 0\), with T for temperature and t for time, the ρ and cp values are not required for heat fluxes through solid materials in steady conditions (see Additional file 1: Appendix S2.1 point D), we use them in the calculations as they are required for the transient approach, with a virtual time factor, used to get a more stable convergence (see Additional file 1: Appendix S2.2) As in this study we are not concerned with the real time needed to reach the steady condition, the temperature and heat flux obtained are applicable to other exterior walls and hung panels provided with correlated conductivity materials and widths (same width * kh).

Outdoor air temperature set for all the simulations is − 3 °C and outdoor heat convection boundary film coefficient has been considered to be 25 W/m2K as recommended for building heat load calculations under normal wind conditions.

Heating by air convection

In order to maintain temperature in the room at 19.6 °C ± 0.3 K (except for the four corners and a narrow area near the exterior wall and the floor) we have simulated a forced convection system blowing air into the room at 20 °C and at 1 m/s for a room 3 m high. In this 2D simulation, the air enters the room through a grille 0.1 m high, located on the upper corner of the opposite wall from the wood panel. The air direction is shifted by the grille − 15 °C from the horizontal axis to counteract part of the Coanda effect. The air is exhausted by an identical grille near the floor level in conservative conditions. Done this way, we achieve a very homogeneous temperature distribution without stratification.

Air supplied in models with rooms 6 m high is blown at 2 m/s and 20 °C (instead of 1 m/s) to compensate heat losses through the exterior wall which is twice the area of the wall 3 m high and to achieve the 19.6 °C ± 0.3 K in the room.

Inside the room the air conduction heat coefficient used in the boundary layer laminar flow is 0.0255 W/m K.

SH scenarios

Two different SH scenarios, both within the range of proper museum conditions, have been set out to calculate the RH values in the different areas of the room, according to the temperatures computed in the CFD models and cases. In this way the channel microclimate was correctly quantified. The conditions for both scenarios are the following:

Scenario SH1: 52% RH in a room heated at 19.6 °C with a Dew Point of 9.7 °C and a SH = 7.5 g water/kg air, which corresponds to high occupation (5 m2/person) + natural infiltration at 1 Volume/h with outside air at − 3 °C and 90% RH.

Scenario SH2: 60% RH in a room heated at 19.6 °C with a Dew Point of 11.9 °C and a SH = 8.7 g water/kg air, which corresponds to middle occupation (8 m2/person) + natural infiltration at 0.5 Volumes/h with outside air at − 3 °C and 90% RH.

RH criteria for the proper conservation of the artistic assets

To guarantee the proper conservation of the artistic assets, the following two criteria have been set: 1) RH in the panel Back must be < 66%; 2) If RH in the Wall = 100%, at least “s” ≥ 2 cm.

The first criterion corresponds to the Smithsonian Institution standard for RH in exhibition rooms released in 2007 [16] which established the range from 37% to 53% and was extended by Erhardt et al. [17] to 30% < RH < 60% after the tests performed on different art materials such as wood, pigments, paint layers, gesso, etc. Also the present ASHRAE conditions [16, 18, 19] can be met with two options for class A (this class foresees small risk of mechanical damage to high vulnerability artifacts and no mechanical risk to most artifacts, paintings, photographs, and books). The first one is RH from 35 to 65% with the set point at 50%, allowing ± 10% seasonal set point variations and ± 5% short term fluctuations. This option allows to extend the RH up to 65%. The second one is RH within the range of 40–60% with 50% as a permanent set point for the whole year and ± 10% short term fluctuations.

Our second criterion—a minimum separation of 2 cm between the panel Back and the Wall when this later is at 100% RH—is under review and it is considered only as a temporary solution in the case that it is impossible to change the painting location or to improve the exterior wall isolation, as it usually happens in some historical buildings.

Actually others standards as EN 15757 [20], EN15759-1 [21] and EN 15759-2 [22] are developed to deal with climate at historical buildings, churches and chapels where wood panels and easel paintings have been submitted to important RH variations along the centuries and have been adapted to the climate conditions showing visible effects such as cracks and flakes or not visible as plastic strains. In these cases, changing the historical climate conditions for others theoretically better may lead to a more endangered condition of the weak artwork.

These standards allow the seasonal RH set point to move in a broader range (safe band), according to the computed mean average (CMA) calculated after 13 months of measured RH inside values and the conservators criteria about the exposed or stored artwork condition, as Camuffo [23, 24], Bratasz [25, 26], Broström et al. [27], Neuhaus and Schellen [28], Schijndel [29] and others have explained.

Today the room RH control in exhibitions and museums varies according to the institutions economic saving policy and energetic goals, the condition and history of exposed or stored objects, the wall materials and air tightness, the importance of the visitors comfort, and other factors.

In order to simplify, in our research we have used, as RH threshold, the maximum allowed value in the ASHRAE standard for the A class. It was not possible to give a universal solution to all the real cases, as this involves studying the endless combinations of temperature and RH possible conditions, the different isolation and thermal inertia of the walls, the unlike building shapes, the varying RH buffers, etc. Our goal is to improve the understanding of heat fluxes, RH and temperatures that take place at the back of wood paintings on exhibition hung in peripheral walls in order to provide conservators with the knowledge to be applied in cases with similar conditions.

Complementary cases

After the analysis of the 45 basic cases, only 3 of them complied the RH values to avoid damages in the artistic asset. Thus, we have extended the simulations to other complementary cases and by a trial and error procedure we have found the distances required, from the panel to the Wall, to comply with the required RH in each layer. In this way we got 9 complementary cases, all of them in the same conditions as before, but not exceeding the 66% RH in both SH scenarios. In the cases of water condensation in the Wall a minimum of 20 mm from Back to Wall is maintained. Also we have extended the simulations to 2 complementary cases by adding 60 mm of expanded polystyrene (EPS) insulation to the exterior wall and to 2 other complementary cases (channel width 8 mm and 20 mm) adding an aluminium protection layer, 0.5 mm thick, at the Back which improves greatly the Back temperatures. As the 8 mm channel width case has a minimum Wall temperature of 7.3 °C (RH = 100%) we cannot recommend it and the 20 mm minimum channel width is recommended for the Wood panel with Aluminium protection. For the isolated wall composition see Table 2.

Table 2 Isolated wall parameters for two complementary cases

Like this, we have extended the general recommendation [3] that states a minimum of 20 mm between a painting and an exterior wall, to more detailed specifications according the different situations. In addition we quantified and clarified the heat transfer modes between the Back and the Wall in these circumstances.

There are other possible variables to take in account, as possible different panel thickness, obstacles to the air flow as cradling, other room or outside temperatures, other inside SH, other geometries, etc., but we have focused in our variables in order to understand and quantify the temperatures, RH and heat fluxes in different conditions, to provide to the conservators the knowledge to understand and deal with the particular conditions they would find.

Calculation procedure. Equations used

The equations used are the conservation of mass (continuity) equation, the conservation of momentum (Navier-Stockes) equations, the conservation of energy (transport equation for enthalpy) equation and the heat transfer through solids (wall and wood panel) equation which it is the Fourier equation but without internal heat production.

All these equations are developed in Additional file 1: Appendix S2.1

The procedure used to solve these equations in a steady flow is shown in Additional file 1: Appendix S2.2

The boundary and initial conditions used to solve these equations are shown in Additional file 1: Appendix S2.3

Results

Temperature and heat flux values in 100 points of the CFD simulation, distributed in the vertical axis along the interface layers—Wall/channel air, channel air/Back, and Front/room air—have been exported for each case.

Also for each of the cases, the temperature and the vertical component (v) of the air velocities have been exported from 20 points distributed horizontally along the channel inlet between the Wall and the panel to compute Ti, the channel inlet air mean temperature (vertical velocity weighed).

For the cases of the model where the wood panel is 50 cm high, the turbulence intensity (Tu) has also been exported in order to compute the turbulence intensity average (Turb) at different heights along the channel. Doing it in this way, the computed heat fluxes have been assigned to the different convection modes (laminar or turbulent) in the detailed analysis of “Heat fluxes and minimum temperatures in the Wall and the Panel Back” section.

In Figs. 2 and 3 the minimum temperatures in the Wall and the Back can be seen for all models and cases.

Fig. 2
figure 2

Wall minimum temperature (basic cases)

Fig. 3
figure 3

Minimum back temperature (basic cases)

Figures 4, 5 and 6 show the averaged heat fluxes for all models and cases. Figure 4 displays the total heat flux received by the Wall, Fig. 5 the heat flux supplied by the Back and Fig. 6 the heat flux supplied directly by the air entering the channel. Figure 7 shows heat flux ratios between Back and Wall (total) and also between Inlet air and Wall (total). In all these graphics heat fluxes and temperatures are plotted versus the “s/h” adimensional number.

Fig. 4
figure 4

Heat flux received in the wall (cases room 3 m high)

Fig. 5
figure 5

Heat flux supplied by back (cases room 3 m high)

Fig. 6
figure 6

Heat flux supplied by inlet air (cases room 3 m high)

Fig. 7
figure 7

Heat flux back and inlet air % (cases room 3 m high)

Table 3 presents all these values for the 45 main cases together with other parameters such as dimensions, plus the inlet air eddy, if it appears. In addition, RH in the Wall, the Back and the Front are included for the scenarios SH1 and SH2.

Table 3 Comparison among models and cases in SH1 and SH2

For complementary information, see Additional file 1: Table S0.1 in Additional file 1: Appendix S0 with more detailed results for each layer (Wall, Back and Front).

Discussion

Heat fluxes and minimum temperatures in the Wall and the Panel Back

In Additional file 1: Appendix S1 there is a detailed analysis of the heat fluxes, turbulence and temperatures at different heights in the channel between Back and Wall for all the cases in a 50 cm high panel. It allows to understand the involved phenomena and temperatures distributions in the channel.

We can see how the Wall temperature decreases as the panel separates from the Wall, due to the laminar flow close to the Wall, and thus the heat flux is only by conduction. Added to the effects of the eddy locations in the channel inlet and channel outlet, the temperature attain a minimum at s = 1.25 mm. As the channel width continues increasing at s = 2.5 mm the outlet eddy change its direction and the Wall is heated enough to compensate the conduction heat flow reduction and the Wall temperature attain a relative maximum.

As the channel width continues increasing at s = 5 mm, it appears another temperature minimum. If the channel width continues increasing and attain s = 7.5 mm, the heat flux to the Wall increases, as inlet air heat flux increases more than the Back heat flux decreases (due to the increasing of inlet air flow and turbulence). This raises the Wall temperatures.

From this point the Back and Wall temperatures increase, approaching the air room temperatures. It is quantified in Additional file 1: Table S1.1 and explained with detail in Additional file 1: Appendix S1.

Figure 2 and Table 3 show how the two Wall temperature minimums discussed in Additional file 1: Appendix S1 for a 50 cm high panel also appear for panels with h = 1 m (4.8 °C and 4.3 °C) and for panels with h = 2 m (4.58 °C and 2.9 °C) in a room 3 m high and for panel with h = 1 m (4 °C and 4.6 °C) in a room 6 m high. As h1 (distance from the panel upper border to the ceiling) increases, the difference between the first minimum Wall temperature and the intermediate maximum decreases. The intermediate maximum nearly disappears for h = 2 m and h1 = 3 m. As h increases, the second minimum is displaced to lower s/h values (to the left side of the curve in Fig. 2).

The explanation is that as h1 increases, more cooled is the air descending close to the Wall and the Ti (average air inlet channel temperature) is lower. Thus, the air layer cooled by the Wall is wider and more air mass is cooled. This can be seen in the Table 3, column Ti(Channel inlet air mean temperature, vertical velocity weighed).

However, the phenomenon is not that simple and other factors shall also be considered.

The air mass flow going into the channel

It can be seen in the special case for h = 2 m, s = 40 mm, where the minimum Wall temperature for ht = 6 m, is higher (6.5 °C) than for ht = 3 m (5.7 °C). For ht = 6 m, the air mean velocity in the channel inlet is 0.6 m/s (at 16.4 °C as average) whereas for ht = 3 m it is 0.3 m/s (at 18 °C average). Thus, being the air mass twice for ht = 6 m and the air temperature only 1.6 K lower, the inlet air thermal energy level is higher for ht = 6 m than for ht = 3 m and it provides enough heat to raise the minimum Wall temperature up to 6.5 °C. When “s” diminishes, as in the case of h = 2 m and s = 20 mm, the minimum Wall temperature is 4 °C for ht = 6 m (inlet velocity 0.4 m/s at 15.2 °C) and 4.5 °C for ht = 3 m (inlet velocity 0.32 m/s at 18.4 °C). In this case, the air velocities are closer and the inlet air thermal energy level is lower for ht = 6 m than for ht = 3 m. An intermediate case is for h = 2 m, s = 30 mm where the minimum Wall temperatures are the same for ht = 6 m and for ht = 3 m (5.2 °C).

The air turbulence in the channel

For small values of “s” (channel width), the air flux is laminar and the heat transfer from the Back is only by conduction. This heat flux diminishes lineally as “s” increases, but as “s” increases more inlet air goes into the channel and the inlet air becomes the heat flux mean supplier to the Wall. As the channel air flow increases the heat flux turns to be turbulent and the addition of the both effects results in the curve “s/h” versus heat flux with a minimum in the zone where the inlet air heat flux starts (s/h between 0.003 and 0.01). This phenomenon can be observed in the three curves of Fig. 4 which are, in turn, composed by the curves of Figs. 5 and 6. The minimum in these curves moves to the right side of the chart as the panel height decreases. In order to further clarify this, Fig. 7 gathers these curves expressed as a percentage.

Also, as shown in Additional file 1: Appendix S1, when the channel is very narrow, air turbulence decreases as the air goes down inside the channel. In these cases, the air flux becomes laminar, still if it has been turbulent just near the channel inlet.

Depending on Temperatures, “s” and “h” parameters, the minimum temperature occurs at mid-height or at the lower zone of the channel. (See Additional file 1: Appendix S0, Table S0.1).

The eddy in the channel inlet

The widening of the air layer descending close to the Wall due to large values of h1 and the narrowing of the channel can form an air eddy in the channel inlet, as more mass of the cooled air descending close to the Wall collides with the top edge of the panel. In this way the air going down close to the Wall gets mixed with the air of the room that enters the channel. This smooths the temperature differences in the channel inlet between the Back and the Wall. The developed eddy is shown in Figs. 8, 9 and 10.

Fig. 8
figure 8

Channel inlet temperature and velocity isolines. Case 28. Panel h = 50 cm. s = 1.25 mm. h1 = 1.25 m. Values at inlet: Tw = 5.7 °C, Tb = 6.7 °C. T average = 6.4 °C. Air channel vertical mean velocity = 0.01 m/s. Δ v between isolines = 0.015 m/s. Inlet eddy

Fig. 9
figure 9

Channel inlet temperature and velocity isolines. Case 27. Panel h = 50 cm. s = 2.5 mm. h1 = 1.25 m. Values at inlet: Tw = 6.8 °C, Tb = 8.6 °C. T average = 8.3 °C. Air channel vertical mean velocity = 0.02 m/s. Δ v between isolines = 0.015 m/s. Inlet eddy

Fig. 10
figure 10

Channel inlet temperature and velocity isolines. Case 25. Panel h = 50 cm. s = 5 mm. h1 = 1.25 m. Values at inlet: Tw = 7.8 °C, Tb = 11.2 °C. T average = 11.4 °C. Air channel vertical mean velocity = 0.09 m/s. Δ v between isolines = 0.015 m/s. Inlet eddy

Table 3 shows in which cases an eddy is developed at the inlet.

The eddy in the channel outlet

Usually one or more air eddies appear in the channel outlet. Depending on the position of these eddies, heated air of the room around the outlet can get mixed with the cooled air of the channel. This may cause heating of the Wall just under the channel. For example, in the case of a panel 50 cm high and a channel width of 2.5 mm (case 27), the Wall under the panel is heated enough by the outlet eddy to send heat flux by conduction through the Wall in vertical direction, raising the minimum temperature in the Wall (see Fig. 11 for s = 2.5 mm). In this same case, this factor explains the maximum of 6.4 °C in the “Wall minimum temperature” compared to the two neighbouring minimums of 5.2 °C that occur when s = 1.25 mm where the eddy is too weak to heat the Wall enough and 5.8 °C when s = 5 mm where the heated air of the room is not sent to the Wall near the channel outlet and, instead, the cooled channel air flows into the room (see Table 3 and Fig. 11 with s = 5 mm).

Fig. 11
figure 11

Velocity isolines and eddys in channel outlet for panels 50 cm height and different widths

Cornices over the panel

In the case of a cornice protruding from the Wall (s = 40 mm, case 37) it can be seen that the minimum temperatures in each layer are at least 3 °C lower that in the case with a straight Wall, due to the air flux deviation at the cornice and the eddy developed below it, that reduces the entrance of hot air from the room to the channel. So, the mean air temperature, vertical velocity weighed at the channel inlet, is reduced from 0.62 to 0.16 m/s (compared to the same geometry without cornice as it is the case 1) and still if the mean air temperature at this point is increased from 16.4 to 16.8 °C, the mean heat flux received by the Wall in the channel drops from 36.1 to 27.9 W/m2 (see Table 3).

In order to compensate the Back and Wall temperature reduction and the heat flux reduction which occurs in this case, and to get the correct temperatures and RH values in the Back, it is necessary to increase the channel width from 40 to 90 mm in scenario SH1 and from 85 to 140 mm in scenario SH2 (see Tables 4 and 5).

Table 4 Minimum “s” distances in scenario SH1
Table 5 Minimum “s” distances in scenario SH2

RH values in the different cases

Table 3 also shows the maximum RH values of the significant layers (Wall, Back and Front) for scenarios SH1 and SH2. In both scenarios condensation appears on the Wall and, in many cases, RH values in the Back are above 66%, which is the limit set for the proper conservation of paintings.

Minimum required distances from a painted wood panel to the exterior wall

From the results of the 3 basic cases, that comply with the two conservation criteria set in Sect. 2.3, and the 13 complementary cases, we got a set of 8 cases for the SH1 scenario (room RH of 52% at 19.6 °C) and other set of 8 cases for the SH2 scenario (room RH of 60% at 19.6 °C) which comply with these conservation criteria. From these 16 cases we got the correct channel widths for all the models analysed.

Table 4 presents the 8 recommended minimum channel widths for the scenario SH1 and Table 5 the same figures for SH2.

It shall be taken in account that changes of the Wall geometry, as cornices protruding above the painted wood panel, or other obstacles to the air flux can modify the recommended minimum separation distances, increasing them.

Attention: If the outside air temperature increases over − 3 °C and the 90% RH is maintained, the SH of the infiltration and ventilations will rise. Therefore the inside room SH and RH will be increased and in this case the recommended channel width shall be increased according the foreseen channel temperatures and the new inside room SH value.

Conclusions

By means of a 2 dimensional CFD simulation of a heated room (19.6 °C) with a painted wood panel hung in the inside face of a non-isolated exterior wall (− 3 °C in the outside face), we have obtained the temperatures, air velocities, and heat fluxes distribution in the channel between the wood panel and the exterior wall, for different wood panel heights, different channel widths, and different distances to the ceiling.

Based on the temperature data results in the wood panel Back and in the Wall, RH values have been obtained at the same locations and for two different SH scenarios (7.5 g water/kg air and 8.7 g water/kg air) corresponding to a room at 52% RH and 60% RH respectively, which are within the normal range of conditions for a museum. From these values, we have established, for the foreseen SH scenarios, the minimum distances between the panel Back and the Wall required to avoid damages in the painted wood panel (RH < 66% in the panel Back) and a minimum of 20 mm in the case there is condensation in the Wall.

In addition, factors that affect temperatures distribution and heat fluxes in the channel have been analysed for series of discrete values in the normal range of use. In the case of a wood panel 50 cm high, these have been discussed in further detail in order to help understand the heat transfer modes involved in the situation.

The study of these factors that modify temperature distribution in both sides of the channel, such as the distance to the ceiling, the channel width, the possible eddy near the channel inlet or outlet, can be used as guidelines to be applied to other similar situations like other model dimensions or possible obstacles to the air flux in the Wall over the wood panel. As examples of this, the effects of a cornice in the Wall or the effects of an aluminium protection layer in the Back of the panel or an EPS 60 mm isolation in the Wall have been quantified to compare with cases without these peculiarities.

This simulation carried out with a commercial 2 dimensional CFD allows to extend the standard 20 mm recommendations for the distances between cold exterior walls and wood panel paintings to a more detailed recommendations for paintings hung on the walls in similar conditions. These recommendations do not entail neither financial costs nor climate variations in the museums and exhibition rooms and conservators can easily apply them.

For the studied cases, Table 3, Back and Wall minimum temperatures and maximum RH values, and Additional file 1: Table S0, Back and Wall minimum temperatures at different heights, show how different these values are from those in the room or near other walls without panels hung on them. When conservators advise how to protect artistic wood panels hung in a poorly insulated peripheral wall, this fact shall be taken into account in addition to the recommendations in the EN standards [20,21,22].

Availability of data and materials

The datasets used and/or analyzed during the current study are available from the corresponding author on reasonable request.

Abbreviations

Wall :

Inner face of the exterior wall

Back :

Wood panel surface facing the Wall

Front :

Wood panel surface facing the room

channel :

Space between Back and Wall

s :

Distance between wall and wood panel, channel width (m)

h :

Wood panel height (m)

s/h :

Ratio channel width/wood panel height

ht :

Room height (m)

h1 :

Distance from ceiling to wood panel upper border (m)

V :

Velocity vector (m/s)

g :

Gravity acceleration vector (m/s2)

I :

Buoyancy force vector = − g (ρρ0) = ρ0gβ (TT0) if ρ Δ T 1(N)

u :

Velocity horizontal component (m/s)

v :

Velocity vertical component (m/s)

x :

Horizontal coordinate m. Origin x = 0 at inner wall (left side). (In Fig. 1)

y :

Vertical coordinate m. Origin y = 0 at floor level. (In Fig. 1)

t :

Time (s)

P :

Pressure (Pa)

P’ :

Pressure correction (Pa)

T :

Temperature (K)

T 0 :

Reference temperature (K)

Tw :

Inner face temperature of the exterior wall (°C)

Tb :

Panel back Temperature (°C)

Ti :

Air channel inlet average temperature, vertical velocity weighed (°C)

Tu :

Turbulence intensity (%) = 100 RMS (v’/v), being v’ fluctuations around the average velocity v

Turb :

Turbulence intensity average at y height, velocity weighed in 20 channel points at the same height (%)

H :

Enthalpy (J)

k :

Kinetic energy (m2/s2)

k h :

Thermal conductivity (W/m K)

cp :

Specific heat or Fluid heat capacity (J/kg K)

δij :

Delta Kronecker (i = j, δij = 1i ≠ j, δij = 0)

Pr :

Prandtl number Pr = µ cp/kh

φ:

Generic property (velocity, temperature, and others)

ρ:

Density (kg/m3)

ρ0 :

Reference density at T0 (kg/m3)

ν :

Kinematic viscosity (m2/s) = µ/ρ

νt :

Computed turbulent kinematic viscosity (m2/s)

µ :

Dynamic viscosity N s/m2 = kg/(m s)

µ t :

Turbulent viscosity N s/m2 = kg/(m s)

λ :

2º coefficient of viscosity (Lamé)

ɛ :

Turbulent kinetic energy dissipation rate (m2/s3)

ω :

Turbulent kinetic energy frequency dissipation (s−1)

β :

Thermal expansion coefficient for perfect gases = 1/Tunits1/K

\(\varGamma = \mu + \mu_{t}\) :

units N s/m2 = kg/(m s)

\(\varGamma_{h}\) :

Heat diffusion coefficient = \(\varGamma_{h} = \left( {\frac{\mu }{\Pr } + \frac{{\mu_{t} }}{{\Pr_{t} }}} \right)c_{p}\)

\(\varPhi\) :

Magnitude to be computed in each cell

RH:

Relative humidity (%)

SH:

Specific or absolute humidity (kg water/kg air)

α1, α2, β1, β2, σk1, σk2, σω1, σω2, σβ, a1 :

Turbulence closure constants

Rr :

Normalized Euclidian residual (general)

Rm :

Normalized Euclidian residual for mass

References

  1. Mecklenburg MF. Micro climates and moisture induced damage to paintings. In: Padfield T, Borchersen K, editors. Museum microclimates conference. The National Museum of Denmark; 2007. p. 19–25.

  2. Neuhaus E. A critical look at the use of HVAC systems in the museum environment. In: Ashley-Smith J, Burmester A, Eibl M, editors. Climate for collections. Standard and uncertainities. Munich: Archetype Publications and Doerner Institut; 2013. p. 117–26.

    Google Scholar 

  3. Padfield T, Berg H, Dahlstrøm N, Rischel A-G. How to protect glazed pictures from climatic insult. In: Vontobel R, editor. ICOM committee for conservation, 13thTriennal Meeting, Rio de Janeiro. London: James & James; 2002. p. 80–5.

    Google Scholar 

  4. Raithby GD, Hollands KGT. Natural Convection. In: Rosenhow, WM, Hartnett, JP, Cho, YI, editors. Handbook of heat transfer. New York: McGraw-Hill; 1998. Vol. 3, chapter 4.

  5. Bar-Cohen A, Rohsenow WM. Thermally optimum spacing of vertical, natural convection cooled, parallel plates. J Heat Transfer. 1984;106(1):116–23.

    Article  Google Scholar 

  6. Cadafalch J, Oliva A, Van der Graaf G, Albets X. Natural Convection in a Large channel with Asymetric Radiative Coupled isothermal Plates. J Heat Transfer. 2003;125(5):812–20.

    Article  Google Scholar 

  7. Launder BE, Spalding DB. Mathematical Models of Turbulence. London-New York: Academic Press; 1972.

    Google Scholar 

  8. Launder BE, Spalding DB. The numerical computation of turbulent flows. Comput Methods Appl Mech Eng. 1974;3(2):269–89.

    Article  Google Scholar 

  9. Gameiro A. EasyCFD_G user’s manual; 2014. http://www.easycfd.net. Accessed June 2017.

  10. Gameiro A. A numerical procedure for 2D fluid flow simulation in unstructured meshes. In: Lopez-Ruiz R, editor. Numerical simulation-from brain imaging to turbulent flows. IntechOpen; 2016. https://www.intechopen.com/books/numerical-simulation-from-brain-imaging-to-turbulent-flows/a-numerical-procedure-for-2d-fluid-flow-simulation-in-unstructured-meshes. Accessed June 2017.

  11. Gameiro A. A 2D software system for expedite analysis of CFD problems in complex geometries. Comput Appl Eng Educ. 2016;24(1):27–38.

    Article  Google Scholar 

  12. Gameiro A. A versatile software tool for the numerical simulation of fluid flow and heat transfer in simple geometries. Comput Appl Eng Educ. 2010;18(1):14–27.

    Google Scholar 

  13. Gameiro A, Villar JA. Numerical simulation of the airflow around airfoils for small wind turbines applications. In: Avilez-Valente P, Carvalho E, Silva Lopes A, editors. V Conferência Nacional de Mecânica dos Fluidos, Termodinâmica e Energia, MEFTE 2014. Porto: AMTAC, FEUP; 2014. p. 21–26.

  14. Gameiro A, Alé JAV, Ferreira A, Da G, Simioni S, Calgaro V. Stall and Pos-Stall of airfoils for small wind turbines: numerical and experimental analysis. In: 14th international conference on wind engineering (ICWE14). Porto Alegre, 2015. http://www.icwe14.org/.

  15. Grau-Bové J, Mazzei L, Strlic M, Cassar M. Fluid simulations in heritage science. Herit Sci. 2019;7:16. https://doi.org/10.1186/s40494-019-0259-9.

    Article  Google Scholar 

  16. Michalski S. Climate guidelines for heritage collections: where we are in 2014 and how we got here. In: Stauderman S, Tompkins WG, editors. Proceedings of the Smithsonian Institution. Summit on the Museum Preservation Environment, 13th–14th March 2013. Washington D.C: Smithsonian Institution Scholarly Press; 2016. p. 7–33.

  17. Erhardt D, Tumosa CS, Mecklenburg MF. Applying science to the question of museum climate. In: Padfield T, Borchersen K, editors. Museum Microclimates. Copenhaguen: National Museum of Denmark; 2007. p. 11–8.

    Google Scholar 

  18. Michalski S. The ideal climate, risk management, the ASHRAE chapter, proofed fluctuations, and towards a full risk analysis model. In: Contribution to the Experts roundtable on sustainable climate management strategies, held in April 2017 in Tenerife, Spain. The Getty Conservation Institute; 2007. https://www.getty.edu/conservation/our_projects/science/climate/paper_michalski.pdf. Accessed 13 June 2017.

  19. Museums, galleries, archives and libraries. In: Owen MS, editor. ASHRAE Handbook—HVAC Applications. Atlanta: ASHRAE-American Society of Heating, Refrigerating and Air Conditioning Engineers Inc.; 2011. Chapter 23, p. 23-1–23-2.

  20. EN 15757 Conservation of cultural property—Specifications for temperatures and relative humidity to limitate the climate-induced mechanical damage in organic hygroscopic materials; 2010. European Committee for Standarisation, Brussels.

  21. EN 15759-1 Conservation of cultural property –Indoor climate—Part 1: guidelines for heating churches, chapels and others places of worship. Brussels: European Committee for Standarisation; 2011.

  22. EN 15759-2 Conservation of cultural property –Indoor climate—Part 2:ventilation in historic buildings and to protect collections. 2018. Brussels: European Committee for Standarisation; 2018.

  23. Camuffo D. Microclimate for cultural heritage. Conservation, restoration and maintenance of indoor and outdoor monuments. Amsterdam: Elsevier; 2019.

    Google Scholar 

  24. Camuffo D, Pagan E, Rissanen S, Bratasz L, Kozlowiski R, Camuffo M, della Valle A. An advanced church heating system favourable to artworks: a contribution to European standarisation. Journal of Cultural Heritage. 2010;11:205–19.

    Article  Google Scholar 

  25. Bratasz L. Allowable microclimate variations in museums and historical buildings: review the guidelines. In: Burmester A, Eibl M, editors. Ashley-Smith J. Climate for collections. Standard and uncertainities. Munich: Archetype Publications and Doerner Institut; 2013. p. 11–9.

    Google Scholar 

  26. Bratasz L. Aceptable and not acceptable microclimate variability: the case of wood. In: Camuffo D, Fassina V, Havermans J, editors. Basic environmental mechanisms affecting cultural heritage. Florence: Nardini; 2010. p. 49–58.

    Google Scholar 

  27. Broström T, Vyhlídal T, Simeunovic G, Klenz Larsen P, Zítek P. Evaluation of different approaches of microclimate control in cultural heritage. In: Ashley-Smith J, Burmester A, Eibl M, editors. Climate for collections. Standard and uncertainities. Munich: Archetype Publications and Doerner Institut; 2013. p. 105–15.

    Google Scholar 

  28. Neuhaus E, Schellen HL. Humidistat controlled heating and ventilation systems to create preservation conditions in historic buildings in the Dutch climate. In Seppänen O, Säteri J, editors. Proceedings of the 9th Clima World Congress Wellbeing Indoors. Volume 9. Helsinki: Finvac; 2007.

  29. Schijndel van AWM. Integrated heat air and moisture modeling and simulation. Eindhoven: Technische Universiteit. https://doi.org/10.6100/ir622370.

Download references

Acknowledgements

Not applicable.

Funding

This research did not receive any specific grant from funding agencies in the public, commercial, or not-for-profit sectors.

Author information

Authors and Affiliations

Authors

Contributions

The order of authors in this paper has been set applying the sequence-determines-credit approach (SDC). SF analyzed and interpreted the data resulting from software and carried out the calculation procedure and was a major contributor in writing the manuscript. GC-F designed the models and scenarios, provided conservation literature background and contributed in the discussion of results. CR-R collaborated in the analysis of data performing the graphics, images and tables and prepared the manuscript for final publication. MOF participated in the discussion of the results from the conservation point of view and contributed significantly in the writing process. All authors read and approved the final manuscript.

Corresponding author

Correspondence to Cristina Ruiz-Recasens.

Ethics declarations

Competing interests

The authors declare that they have no competing interests.

Additional information

Publisher's Note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Supplementary information

Additional file 1.

Appendices.

Rights and permissions

Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/. The Creative Commons Public Domain Dedication waiver (http://creativecommons.org/publicdomain/zero/1.0/) applies to the data made available in this article, unless otherwise stated in a credit line to the data.

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Ferrer, S., Campo-Francés, G., Ruiz-Recasens, C. et al. Microclimate numerical simulation to obtain the minimum safe distances between a painted wood panel and the inner face of an exterior wall. Herit Sci 8, 34 (2020). https://doi.org/10.1186/s40494-020-00376-1

Download citation

  • Received:

  • Accepted:

  • Published:

  • DOI: https://doi.org/10.1186/s40494-020-00376-1

Keywords